Showing posts with label Pumping systems. Show all posts
Showing posts with label Pumping systems. Show all posts

Friday, September 13, 2019

WASTE WATER FLOW CAPACITY - In sewage piping and pumping systems, the flow velocity must exceed certain limits to maintain trouble free operation and to avoid settling and sedimentation of solids. On the other hand, the flow velocity should not exceed certain limits to avoid potential wear and tear due to erosion and abrasion.

Image result for images Waste Water - Flow Capacity
................................................................................................................
Image result for images Waste Water - Flow Capacity
Waste Water - Flow Capacity
The Engineering ToolBox




In sewage piping and pumping systems, the fluid flow rate must be kept within certain limits to avoid operating problems
In sewage piping and pumping systems, the flow velocity must exceed certain limits to maintain trouble free operation and to avoid settling and sedimentation of solids:
·          for horizontal wastewater pipe systems with solids the speed should exceed 3 ft/sec
·          for wastewater water system with organic solids the speed should exceed 2 ft/sec
On the other hand, the flow velocity should not exceed certain limits to avoid potential wear and tear due to erosion and abrasion:
·          the flow velocity in high-grit sewage handling systems should not exceed 12 ft/sec
·          the flow velocity in sewage systems with low grit concentrations should not exceed 18 ft/sec
Flow rate capacities in US gal for sewage piping and pumping systems within the limitations:
Flow Rate (US GPM) 
Pipe Dimension
(inches)
Minimum Velocity
Maximum Velocity
2 ft/sec
(0.6 m/s)
3 ft/sec
(0.9 m/s)
12 ft/sec
(3.6 m/s)
18 ft/sec
(5.4 m/s)
3
45
65
270
400
4
80
120
480
700
6
180
260
1050
1600
8
300
500
1900
2800
10
500
750
3000
4400
12
700
1100
4300
6400
Note! - based on clean pipes. The friction coefficient may vary with the pipe material.
·                     Unit Converter

About the ToolBox
We appreciate any comments and tips on how to make The Engineering ToolBox a better information source. Please contact us by email

Image result for images Waste Water - Flow Capacity

Monday, August 7, 2017

WATER HAMMER - Water hammer is a phenomenon that occurs in many pumping systems, sometimes having minimal effect, and other times catastrophic. Let’s say a valve is closed quickly. The flow of the water has been interrupted and has nowhere else to go, and collides against the closed valve. Because water is not very compressible, it creates a pressure, or shock wave, then reverses flow, back upstream. Should the wave then run into a pump upstream, the fluid will continue to travel back and forth until friction losses cause the wave to settle. Throughout this process, the shockwaves have sent vibrations through the system.

Water 
Hammer
What Is Water Hammer
Sara Peters




Water hammer is a phenomenon that occurs in many pumping systems, sometimes having minimal effect, and other times catastrophic.
If not carefully planned for, water hammer can cause thousands of dollars in damage and lost productivity.
So what is water hammer anyway?
According to a Pumps and Systems article, published in August 2008, “water hammer is a pressure surge that can arise in any pumping system that undergoes an abrupt change in its rate of flow and usually results from pump starts and stops, the opening and closing of valves, or water column separation and closure.”
When these abrupt changes are inflicted on a system, they cause the fluid to undergo a change in momentum.
Let’s look at an example. Let’s say a valve is closed quickly to isolate flow of water.
The flow of the water has been interrupted and has nowhere else to go, and collides against the closed valve.
Because water is not very compressible, it creates a pressure, or shock wave, then reverses flow, back upstream.
Should the wave then run into a pump upstream, the fluid will continue to travel back and forth until friction losses cause the wave to settle.
Throughout this process, the shockwaves have sent vibrations through the system.
The size of the shockwaves is dependent upon 3 factors: the velocity of the fluid in ft/sec (V), the length of the pipe between barriers in feet (L), and the amount of time it took to close the valve in seconds (t).
The intensity of the shockwave can be calculated by this equation, (offered in article from Blacoh U): P=0.07(VL/t), where P is the resulting additional pressure generated by the shock wave.
(Additional water hammer calculators can be found in a previous post, “3 Calculators For Water Hammer And Pressure Drop.)
Let’s take our example and plug it into the equation.
The fluid is moving at 5 feet per second, and the length of pipe between our two valves is 500 feet. Our actuator has quickly closed the valve at .5 seconds.
The resulting pressure from the shock wave is as follows:
0.07(5 x 500)/.5 = 350 PSI
Most systems are not designed to handle such great additional pressures as those generated by water hammer.
For a more in-depth study of water hammer, head out to Blacoh U and create an account for access to a 30 minute video "The Phenomenon Called Water Hammer".
When you abruptly close valves, listen for loud noises or vibration and pulsation of pipes.
If you hear or see what looks like the effects of water hammer, be sure to consult an experienced engineer.
They can help you put some fixes in place to keep your system intact.
Got a problem with water hammer? Ask us about it! We gladly provide technical assistance to businesses in Wisconsin and Upper Michigan.
Sara Peters leads Crane Engineering's blogging team, coming up with fresh stories and insights for our readers to apply to their every day work.
You might also like:
.

Pressure
Tanks
What Are They and How Do They Work?
CLICK HERE . . .

Pressure and Fluid 
Flow
How Does Pressure Relate to Fluid Flow?
CLICK HERE . . .
.
Hydrocyclones

.
.
.
.
.
.
.
.

CLICK HERE . . .
..
Multi-Media Filter, Highly-Activated Carbon Filter,
Zeolite-Process Water Softener With Brine Tank,
Fiberglass Ballast-Type Pressure Tank
(fully automatic backwash & regeneration)
PURICARE 
INDUSTRIAL 
ENTERPRISES 
Water 
Treatment 
Systems
.
.
...
Aganan, Pavia, Iloilo, Philippines